UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
4 User Interface
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
189
Item
Description
–5°C. The
Overtemp. alarm thresh.
can be set from 35°C to 55°C
and the default value is 50°C.
Figure 4-45
Battery Param. screen 4
Item
Description
Backup time warning
An alarm is generated if this parameter is set to
Enable
and
the backup time is less than the warning threshold. The
default value is
Disable
.
Remain. cap. warning
An alarm is generated if this parameter is set to
Enable
and
the remaining capacity is less than the warning threshold. The
default value is
Disable
.
Dis. cur. 0.1C EOD
(V/cell)
,
Dis. cur. 0.3C
EOD (V/cell)
,
Dis. cur.
0.5C EOD (V/cell)
, and
Dis. cur. 1.0C EOD
(V/cell)
By default,
0.1C EOD (V/cell)
is set to
1.80
,
0.3C EOD
(V/cell)
to
1.80
,
0.5C EOD (V/cell)
to
1.75
, and
1.0C EOD
(V/cell)
to
1.60
. These values are calculated in real time based
on the discharge currents.