UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
4 User Interface
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
191
Figure 4-47
Battery Param. screen 6
Item
Description
Bat mode shut
In battery mode, the UPS can automatically power off according to
the preset shutdown delay time. If the parameter is disabled, this
function is not available. The default value is
Disable
.
Dry Contact Settings
Set only the dry contacts that are needed. Otherwise, the UPS may not run properly.
When a dry contact card is disabled, its dry contact signals are disabled.
After a dry contact card is enabled, its dry contact signals can be displayed on the LCD.
Disable all the dry contacts for a dry contact card that is not connected and all the dry
contacts that are not used to prevent false alarms.
( ) encloses a unit, and [ ] encloses silk screen.
Specify dry contact settings on the following cards:
Dry contact card (MUE05A): provides dry contact signals for the battery grounding
failure detector, D.G., BCB box, and PDCs.
Backfeed protection board (MUE06A): provides backfeed protection signals. This board
can be enabled or disabled.
Monitoring interface card (MUS05A): provides four routes of configurable output dry
contact signals.
Dry contact extended card (MUE07A): provides two routes of input signals and one
route of output signals.
Set the dry contact parameters, as shown in
to