UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
8 Technical Specifications
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
280
Safety and
EMC
400 kVA
500 kVA
600 kVA
800 kVA
IEC61000-2-2
IEC61000-4-2
IEC61000-4-4
IEC61000-4-5
EN61000-4-3
EN61000-4-6
IEC61000-4-8
8.5 Mains Input Electrical Specifications
Item
400 kVA
500 kVA
600 kVA
800 kVA
Input system
Three-phase, four-wire, and PE
Rated input
voltage
380 V AC, 400 V AC, or 415 V AC (line voltage)
Input voltage
80–280 V AC (phase voltage)
At 40°C: The UPS works at full load when the voltage is 187–280 V
AC and is derated to 40% load when the voltage is 187–80 V AC.
At 30°C: The UPS works at full load when the voltage is 176–280 V
AC and is derated to 40% load when the voltage is 176–80 V AC.
Rated
frequency
50 Hz or 60 Hz
Input
frequency
40–70 Hz
Input PF
> 0.99 (full load)
> 0.98 (half load)
THDi
THDi < 3% (full linear load)
THDi < 5% (full non-linear load)
8.6 Bypass Input Electrical Specifications
Item
400 kVA
500 kVA
600 kVA
800 kVA
Input system
Three-phase, four-wire, and PE
Rated input
380 V AC, 400 V AC, or 415 V AC (line voltage)