UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
4 User Interface
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
180
Item
Description
(A)
limit
is set to 0 A, the power module does not perform inverter capacitor
fault detection. The default value is
2.5 A
.
Input cur.
limiting
Specifies whether to enable or disable input current limiting to protect
generators. The default value is
Disable
.
Input cur.
limiting ratio
(%)
Limits the input current to protect the D.G. The value can be 50%–200%.
The default value is 200%.
No load
output shows
zero
If this parameter is set to
Enable
, the output current and output load ratio
are displayed as 0 in the case of no load. If this parameter is set to
Disable
, the output current and output load ratio are not displayed as 0 in
the case of no load. The default value is
Enable
.
Current
equal.
detection
Monitors the current differences between racks or modules. If this
parameter is set to
Enable
, the
Mod. Cur. Eql. Data
can be viewed on
the running information screen. This parameter is set to
Disable
by
default.
Bus Capa.
Life
If this parameter is set to
Enable
, the UPS detects the bus capacitor
lifespan. The default value is
Disable
.
Figure 4-37
Advanced Param. screen 5
Item
Description
Altitude
(m)
Set this parameter based on the altitude of the place where the rack is used.
The default value is less than or equal to 1000.
ModbusTC
P
Encryption
If Modbus TCP is used for communication, communication links do not
implement encryption or implement encryption based on the selected
encryption mode. The default value is
Enable
.
Air filter
maintenanc
Specifies the rack air filter maintenance interval. If it is set to
0
, there is no
reminder. The value range is 0 to 365. The default value is
0
.