Alar
m ID
Alarm
Severit
y
Alarm Name
Probable Cause
Solution
A291
-02
MAJOR
Compressor 1
overcurrent
alarm
1. The compressor
lacks oil.
2. The condenser
fins are dirty or
blocked.
3. The outdoor fan
is abnormal.
4. The refrigerant is
overfilled.
5. The compressor is
faulty.
1. Fill oil to the
compressor.
2. Clean the condenser
fins.
3. Maintain or replace
the outdoor fan.
4. Decrease certain
amount of refrigerant.
5. Maintain or replace
the compressor.
A291
-02
MAJOR
Compressor 2
overcurrent
alarm
1. The compressor
lacks oil.
2. The condenser
fins are dirty or
blocked.
3. The outdoor fan
is abnormal.
4. The refrigerant is
overfilled.
5. The compressor is
faulty.
1. Fill oil to the
compressor.
2. Clean the condenser
fins.
3. Maintain or replace
the outdoor fan.
4. Decrease certain
amount of refrigerant.
5. Maintain or replace
the compressor.
A296
-01
CRITICA
L
EEV 1 low
superheat
degree alarm
1. The electronic
expansion valve
(EEV) coil is loose.
2. The EEV coil is
faulty.
3. The cables to the
electronic expansion
valve coil are loose
or damaged.
4. The EEV is faulty.
1. Reinstall the EEV
coil.
2. Replace the EEV coil.
3. Check and maintain
the cables to the EEV
coil.
4. Replace the EEV.
A296
-01
CRITICA
L
EEV 2 low
superheat
degree alarm
1. The electronic
expansion valve
(EEV) coil is loose.
2. The EEV coil is
faulty.
3. The cables to the
electronic expansion
valve coil are loose
or damaged.
4. The EEV is faulty.
1. Reinstall the EEV
coil.
2. Replace the EEV coil.
3. Check and maintain
the cables to the EEV
coil.
4. Replace the EEV.
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
6 System Operation and Maintenance
Issue 06 (2020-08-19)
Copyright © Huawei Technologies Co., Ltd.
200