Alar
m ID
Alarm
Severit
y
Alarm Name
Probable Cause
Solution
A26B
-04
MAJOR
Indoor fan 3
power supply
abnormal
1. The cable to the
fan is not connected
properly.
2. The fan is faulty.
1. Check the cable
connection to the fan.
2. Maintain or replace
the fan.
A26B
-04
MAJOR
Indoor fan 4
power supply
abnormal
1. The cable to the
fan is not connected
properly.
2. The fan is faulty.
1. Check the cable
connection to the fan.
2. Maintain or replace
the fan.
A26B
-04
MAJOR
Indoor fan 5
power supply
abnormal
1. The cable to the
fan is not connected
properly.
2. The fan is faulty.
1. Check the cable
connection to the fan.
2. Maintain or replace
the fan.
A26B
-04
MAJOR
Indoor fan 6
power supply
abnormal
1. The cable to the
fan is not connected
properly.
2. The fan is faulty.
1. Check the cable
connection to the fan.
2. Maintain or replace
the fan.
A26B
-04
MAJOR
Exhaust fan 1
power supply
abnormal
1. The cable to the
fan is not connected
properly.
2. The fan is faulty.
1. Check the cable
connection to the fan.
2. Maintain or replace
the fan.
A26B
-04
MAJOR
Exhaust fan 2
power supply
abnormal
1. The cable to the
fan is not connected
properly.
2. The fan is faulty.
1. Check the cable
connection to the fan.
2. Maintain or replace
the fan.
A26B
-04
MAJOR
Exhaust fan 3
power supply
abnormal
1. The cable to the
fan is not connected
properly.
2. The fan is faulty.
1. Check the cable
connection to the fan.
2. Maintain or replace
the fan.
A26B
-04
MAJOR
Exhaust fan 4
power supply
abnormal
1. The cable to the
fan is not connected
properly.
2. The fan is faulty.
1. Check the cable
connection to the fan.
2. Maintain or replace
the fan.
A26B
-04
MAJOR
Exhaust fan 5
power supply
abnormal
1. The cable to the
fan is not connected
properly.
2. The fan is faulty.
1. Check the cable
connection to the fan.
2. Maintain or replace
the fan.
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
6 System Operation and Maintenance
Issue 06 (2020-08-19)
Copyright © Huawei Technologies Co., Ltd.
170