Menu
Parameter
Setting Guide
Default Value
Smart
cooling
product
address
Set the assigned unit
address.
NA
Enable
Teamwork
CAN resistor
● Set this parameter to
No for non-teamwork
scenarios.
● For teamwork
scenarios, set this
parameter to Yes for
the first and last
smart cooling
products in a
teamwork group, and
set it to No for other
smart cooling
products.
No
Teamwork
function
Set this parameter based
on the onsite device heat
distribution.
Disable
Networking
mode
Networked over CAN or
MAC_CAN. CAN
network indicates
teamwork control over a
CAN bus, MAC_CAN
network teamwork
control over an FE port.
CAN network
Number of
smart
cooling
products in
this group
Total number of the
smart cooling products in
this group.
3
Number of
running
smart
cooling
products in
this group
The host allocates
running units by smart
cooling product unit
address in ascending
order, which is from 1 to
32. The rest will become
the standby ones.
2
Rotation
function
This function is
recommended when the
heat is even.
Disable
Rotation
period
7 by default
7 day (s)
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
4 Power-on and Commissioning
Issue 06 (2020-08-19)
Copyright © Huawei Technologies Co., Ltd.
79