Alar
m ID
Alarm
Severit
y
Alarm Name
Probable Cause
Solution
A185
-01
WARNI
NG
Compressor 1
Insufficient
refrigerant
alarm
1. Refrigerant has
leaked.
2. Refrigerant is not
charged as required
in the user manual.
3. The displayed
values of the liquid
pipe temperature
sensor or the
condensing pressure
sensor on the LCD
are different from
the actual values.
1. Check the system for
leaking points. If so,
repair the pipe and add
refrigerant.
2. Add refrigerant as
required in the user
manual.
3. Calibrate or replace
the liquid pipe
temperature sensor or
the condensing
pressure sensor.
A185
-01
WARNI
NG
Compressor 2
Insufficient
refrigerant
alarm
1. Refrigerant has
leaked.
2. Refrigerant is not
charged as required
in the user manual.
3. The displayed
values of the liquid
pipe temperature
sensor or the
condensing pressure
sensor on the LCD
are different from
the actual values.
1. Check the system for
leaking points. If so,
repair the pipe and add
refrigerant.
2. Add refrigerant as
required in the user
manual.
3. Calibrate or replace
the liquid pipe
temperature sensor or
the condensing
pressure sensor.
A193
-01
MAJOR
Air-side diff
pressure
sensor fault
1. The differential
pressure sensor
cable is loose or
damaged.
2. The pressure tube
of the differential
pressure sensor is
reversely connected.
3. The differential
pressure sensor is
faulty.
1. Check the cable
connection to the
differential pressure
sensor.
2. Check the tube
connection to the
differential pressure
sensor.
3. Maintain or replace
the differential
pressure sensor.
A208
-01
MAJOR
Indoor fan 1
blocked alarm
1. The fan blade is
stuck.
2. The fan is faulty.
1. Clear the blockage.
2. Maintain or replace
the fan.
A208
-01
MAJOR
Indoor fan 2
blocked alarm
1. The fan blade is
stuck.
2. The fan is faulty.
1. Clear the blockage.
2. Maintain or replace
the fan.
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
6 System Operation and Maintenance
Issue 06 (2020-08-19)
Copyright © Huawei Technologies Co., Ltd.
165