Alar
m ID
Alarm
Severit
y
Alarm Name
Probable Cause
Solution
A296
-02
CRITICA
L
EEV 1 low
superheat
degree alarm
1. The electronic
expansion valve
(EEV) coil is loose.
2. The EEV coil is
faulty.
3. The EEV is faulty.
4. The cables to the
electronic expansion
valve coil are loose
or damaged.
1. Reinstall the EEV
coil.
2. Replace the EEV coil.
3. Replace the EEV.
4. Check and maintain
the cables to the EEV
coil.
A296
-02
CRITICA
L
EEV 2 low
superheat
degree alarm
1. The electronic
expansion valve
(EEV) coil is loose.
2. The EEV coil is
faulty.
3. The EEV is faulty.
4. The cables to the
electronic expansion
valve coil are loose
or damaged.
1. Reinstall the EEV
coil.
2. Replace the EEV coil.
3. Replace the EEV.
4. Check and maintain
the cables to the EEV
coil.
A298
-01
MAJOR
Spray
overflow
alarm
1. The spray
overflow pipe is
dirty or blocked.
2. The float does
not drop because
the spray high float
is faulty.
1. Clear the spray
overflow pipe.
2. Maintain the spray
high float.
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
6 System Operation and Maintenance
Issue 06 (2020-08-19)
Copyright © Huawei Technologies Co., Ltd.
201