Alar
m ID
Alarm
Severit
y
Alarm Name
Probable Cause
Solution
A28D
-02
CRITICA
L
Comp 1 low
suction
pressure
alarm
1. The refrigerant
leaks.
2. The pressure
displayed is
different from the
actual pressure.
3. The filter dryer is
blocked.
4. The expansion
valve is blocked or
stuck, or the
expansion valve coil
and cable
connections are
faulty.
5. The indoor fan is
faulty.
6. The ambient
temperature is
below the lower
threshold.
1. Identify and repair
the leaking point, and
refill refrigerant after
maintenance.
2. Calibrate or replace
the pressure sensor.
3. Maintain or replace
the filter dryer.
4. Maintain or replace
the expansion valve or
the coil, and reconnect
cables.
5. Maintain or replace
the indoor fan.
6. Measure the
ambient temperature.
A28D
-02
CRITICA
L
Comp 2 low
suction
pressure
alarm
1. The refrigerant
leaks.
2. The pressure
displayed is
different from the
actual pressure.
3. The filter dryer is
blocked.
4. The expansion
valve is blocked or
stuck, or the
expansion valve coil
and cable
connections are
faulty.
5. The indoor fan is
faulty.
6. The ambient
temperature is
below the lower
threshold.
1. Identify and repair
the leaking point, and
refill refrigerant after
maintenance.
2. Calibrate or replace
the pressure sensor.
3. Maintain or replace
the filter dryer.
4. Maintain or replace
the expansion valve or
the coil, and reconnect
cables.
5. Maintain or replace
the indoor fan.
6. Measure the
ambient temperature.
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
6 System Operation and Maintenance
Issue 06 (2020-08-19)