Alar
m ID
Alarm
Severit
y
Alarm Name
Probable Cause
Solution
A002
-01
CRITICA
L
Return air
high
temperature
alarm
1. The temperature
sensors or
temperature and
humidity sensors
are located in
inappropriate
positions.
2. The thermal load
power is high or the
cooling capacity is
insufficient.
3. The ambient
temperature
exceeds the upper
threshold.
4. The high
temperature alarm
threshold is
inappropriate.
5. The value
detected by the
temperature sensor
or temperature and
humidity sensor is
different from the
actual value.
6. The chilled water
flow is insufficient,
or the supply water
temperature is high.
7. The chilled water
valve is stuck or
faulty.
1. Adjust the positions
of the temperature
sensors or temperature
and humidity sensors.
2. Add air conditioners
or contact Huawei
technical support.
3. Measure the
ambient temperature.
Check whether other
causes exist if the
alarm persists in a long
time after startup.
4. Adjust the high
temperature alarm
threshold.
5. Calibrate or replace
the temperature sensor
or temperature and
humidity sensor.
6. Check the pressure
and temperature of
chilled water.
7. Maintain or replace
the chilled water valve.
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
6 System Operation and Maintenance
Issue 06 (2020-08-19)
Copyright © Huawei Technologies Co., Ltd.
135