Alar
m ID
Alarm
Severit
y
Alarm Name
Probable Cause
Solution
A120
-01
MAJOR
Exhaust fan 4
communicatio
n failure
1. The
communications
cable to the fan is
not connected
properly.
2. The fan is faulty.
1. Check the
communications cable
connection to the fan.
2. Maintain or replace
the fan.
A120
-01
MAJOR
Exhaust fan 5
communicatio
n failure
1. The
communications
cable to the fan is
not connected
properly.
2. The fan is faulty.
1. Check the
communications cable
connection to the fan.
2. Maintain or replace
the fan.
A120
-01
MAJOR
Exhaust fan 6
communicatio
n failure
1. The
communications
cable to the fan is
not connected
properly.
2. The fan is faulty.
1. Check the
communications cable
connection to the fan.
2. Maintain or replace
the fan.
A134
-01
MAJOR
Compressor 1
suction
temperature
sensor fault
1. The cables to the
suction temperature
sensor are loose or
damaged.
2. The suction
temperature sensor
is faulty.
1. Check cables to the
suction temperature
sensor.
2. Maintain or replace
the suction
temperature sensor.
A134
-01
MAJOR
Compressor 2
suction
temperature
sensor fault
1. The cables to the
suction temperature
sensor are loose or
damaged.
2. The suction
temperature sensor
is faulty.
1. Check cables to the
suction temperature
sensor.
2. Maintain or replace
the suction
temperature sensor.
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
6 System Operation and Maintenance
Issue 06 (2020-08-19)
Copyright © Huawei Technologies Co., Ltd.
163