Alar
m ID
Alarm
Severit
y
Alarm Name
Probable Cause
Solution
A281
-80
MAJOR
Power voltage
abnormal
1. The power supply
voltage exceeds the
upper threshold.
2. The SPD and
voltage detection
board is faulty.
1. Check that the
power supply voltage is
within the operating
range.
2. Replace the SPD and
voltage detection
board.
A281
-80
MAJOR
Backup power
voltage
abnormal
1. The power supply
voltage exceeds the
upper threshold.
2. The SPD and
voltage detection
board is faulty.
1. Check that the
power supply voltage is
within the operating
range.
2. Replace the SPD and
voltage detection
board.
A282
-02
CRITICA
L
Power phase
sequence
abnormal
1. The phase
sequence of the
power supply is
incorrect.
2. The SPD and
voltage detection
board is faulty.
1. Rectify the phase
sequence of the power
supply.
2. Maintain or replace
the SPD and voltage
detection board.
A282
-02
MAJOR
Backup power
phase
sequence
abnormal
1. The phase
sequence of the
power supply is
incorrect.
2. The SPD and
voltage detection
board is faulty.
1. Rectify the phase
sequence of the power
supply.
2. Maintain or replace
the SPD and voltage
detection board.
A282
-04
CRITICA
L
Power phase
sequence
abnormal
1. The power grid is
unstable.
2. The phase A
input cable is faulty.
1. Check the power
grid.
2. Rectify the fault of
the phase A input
cable.
A282
-04
MAJOR
Backup power
phase
sequence
abnormal
1. The power grid is
unstable.
2. The phase A
input cable is faulty.
1. Check the power
grid.
2. Rectify the fault of
the phase A input
cable.
NetCol8000-E220 Modular Indirect Evaporative