4.4 Initial Configuration
NO TICE
● When configuring the temperature and humidity parameters, do not place the
cursor between the decimal point and the following digit of the value.
Otherwise, the decimal point cannot be deleted, and the parameter value fails
to be configured.
● When no air damper is configured, do not enable the air damper function.
Otherwise, the air damper communication failure alarm will be generated,
causing the device to work abnormally.
4.4.1 Setting Temperature and Humidity Values and Enabling
T/H Sensors
Prerequisites
●
The T/H sensors outside the cabinet need to be enabled when they are
installed, otherwise, skip
.
●
If you need to enable a humidity and temperature sensor, log in as the admin
user.
●
This section describes how to enable Cold aisle sensor 1.
Procedure
Step 1 On the home screen, choose Settings > System Settings > T/H sensor.
is displayed.
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual