Alar
m ID
Alarm
Severit
y
Alarm Name
Probable Cause
Solution
A308
-01
WARNI
NG
Spray water
pump 2
exceed
runtime
alarm
The accumulated
runtime the spray
pump exceeds the
alarm threshold.
1. Replace the pump
and clear the
accumulated runtime.
A30C
-01
WARNI
NG
Certificate is
about to
expire
1. The
corresponding
certificate is about
to expire.
2. The system time
is incorrectly set.
1. Apply for a new
certificate promptly
and update the
existing one.
2. Calibrate the system
time.
A30C
-02
WARNI
NG
Certificate is
about to
expire
1. The
corresponding
certificate is about
to expire.
2. The system time
is incorrectly set.
1. Apply for a new
certificate promptly
and update the
existing one.
2. Calibrate the system
time.
A30C
-04
WARNI
NG
Certificate is
about to
expire
1. The
corresponding
certificate is about
to expire.
2. The system time
is incorrectly set.
1. Apply for a new
certificate promptly
and update the
existing one.
2. Calibrate the system
time.
A30D
-01
WARNI
NG
Certificate is
not in effect
1. The installed
corresponding
certificate does not
take effect.
2. The connection
of the
corresponding
certificate server is
abnormal.
3. The
corresponding
certificate is not
within the validity
period.
1. Ensure that the
certificate is correctly
installed.
2. Ensure that the
connection of the
certificate server is
normal.
3. Ensure that the
installed certificate is
within the validity
period.
A30E
-01
WARNI
NG
Certificate has
expired
1. The
corresponding
certificate has
expired.
2. The system time
is incorrectly set.
1. Apply for a new
certificate promptly
and update the
existing one.
2. Calibrate the system
time.
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
6 System Operation and Maintenance
Issue 06 (2020-08-19)
Copyright © Huawei Technologies Co., Ltd.
204