Menu
Name
Description
Default Value
DO association
● When DO associated
alarm is set to
Smoke&Water only, if
a smoke sensor alarm
or water overflow alarm
is generated, port 1 for
reporting common
alarms generates a dry
contact close alarm, and
port 2 for reporting
common alarms does
not function.
● When DO associated
alarm is set to
Critical&Major alarm,
if a critical alarm is
generated, port 1 for
reporting common
alarms generates a dry
contact close alarm; if a
major alarm is
generated, port 2 for
reporting common
alarms generates a dry
contact close alarm.
● When DO associated
alarm is set to No, ports
1 and 2 for reporting
common alarms are
open and generate no
alarms.
Smoke &
Water only
Smart diagnosis
function
The smart diagnosis
function can be set to
Enable or Disable.
Disable
Floor water
overflow alarm
action
Shutdown, Inactiveity,
Only indoor fan running,
or Humidification
stopped can be set as
required.
Humidification
stopped
Dual power
supply setting
Select Primary power first
or Primary power only.
Set this parameter as
required.
Primary power
first
Power limit
function
Select Enable or Disable.
The default value is
recommended.
Disable
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
C Parameter Description
Issue 06 (2020-08-19)
Copyright © Huawei Technologies Co., Ltd.
259