Alar
m ID
Alarm
Severit
y
Alarm Name
Probable Cause
Solution
A077
-20
MAJOR
Exhaust fan 4
fault
1. The ground cable
to the fan is not
connected properly.
2. The fan is faulty.
1. Check the ground
cable connection to the
fan.
2. Maintain or replace
the fan.
A077
-20
MAJOR
Exhaust fan 5
fault
1. The ground cable
to the fan is not
connected properly.
2. The fan is faulty.
1. Check the ground
cable connection to the
fan.
2. Maintain or replace
the fan.
A077
-20
MAJOR
Exhaust fan 6
fault
1. The ground cable
to the fan is not
connected properly.
2. The fan is faulty.
1. Check the ground
cable connection to the
fan.
2. Maintain or replace
the fan.
A089
-01
MAJOR
Compressor 1
drive speed
limit alarm
1. The compressor
lacks oil.
2. The refrigerant
leaks.
1. Fill oil to the
compressor.
2. Identify and repair
the leaking point, and
refill refrigerant after
maintenance.
A089
-01
MAJOR
Compressor 2
drive speed
limit alarm
1. The compressor
lacks oil.
2. The refrigerant
leaks.
1. Fill oil to the
compressor.
2. Identify and repair
the leaking point, and
refill refrigerant after
maintenance.