Table 4-8 Teamwork settings
Paramete
r
Description
Configuration
Principle
Default
Value
Teamwork
group No.
The number of the
teamwork controlled
group, which is the same
for all the devices in the
group.
Set the assigned
teamwork control
number.
1
Smart
cooling
product
address
Smart cooling product
addresses should be
different from each
other.
Set the assigned unit
address.
NA
Enable
Teamwork
CAN
resistor
Indicates the build-out
resistor status of each
smart cooling product in
a teamwork group. Set
the parameter if CAN
network is used.
● Set this parameter
to No for non-
teamwork scenarios.
● For teamwork
scenarios, set this
parameter to Yes
for the first and last
smart cooling
products in a
teamwork group,
and set it to No for
other smart cooling
products.
No
Teamwork
function
Disable or enable the
teamwork function. If
the teamwork function is
disabled, this device is
operating according to
its own control. If the
teamwork function is
enabled, this device
works in harmony with
others that in the same
group.
Set this parameter
based on the onsite
device heat
distribution.
Disable
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
4 Power-on and Commissioning
Issue 06 (2020-08-19)
Copyright © Huawei Technologies Co., Ltd.
98