NO TICE
Before performing any operation on the smart cooling product, disconnect the
power supply.
Table 6-6 Troubleshooting of common faults
Symptom
Possible Cause
Solution
Air leakage
The connection nut is
loose due to long-
distance transportation.
Tighten the nut.
The smart cooling
product is deformed
after being improperly
transported or installed.
Adjust the installation
position of the smart
cooling product.
Water leakage
Excessively large air
volume causes the water
to move out.
Adjust the air volume
and add a water pan.
The water pan is not
properly drained.
The base is not properly
installed.
Level the base.
The drainpipe does not
have a water trap or
does not meet the
requirements.
Install or adjust the
water trap.
The fan is not properly
running.
The fan bearing is worn
out.
Repair or replace the
bearing.
The fan blade is
interfered with the shell.
Adjust the fan blade.
The return air damper is
shaking.
Adjust the return air
damper.
There are foreign
matters.
Clear the foreign
matters.
The air volume is
excessively large.
The external static
pressure is excessively
small (the air duct is
excessively short).
Rebalance the air
volume and air pressure.
The rotational speed is
too high.
Adjust the voltage again.
The motor is burnt.
The motor is overloaded. Balance the air volume
and replace the motor.