Alar
m ID
Alarm
Severit
y
Alarm Name
Probable Cause
Solution
A30E
-02
WARNI
NG
Certificate has
expired
1. The
corresponding
certificate has
expired.
2. The system time
is incorrectly set.
1. Apply for a new
certificate promptly
and update the
existing one.
2. Calibrate the system
time.
A30E
-04
WARNI
NG
Certificate has
expired
1. The
corresponding
certificate has
expired.
2. The system time
is incorrectly set.
1. Apply for a new
certificate promptly
and update the
existing one.
2. Calibrate the system
time.
A30F
-01
MAJOR
Air-side
differential
pressure
sensor
communicatio
n failure
1. The differential
pressure sensor
cable is loose or
damaged.
2. The DIP switch of
the differential
pressure sensor is
set incorrectly.
3. The differential
pressure sensor is
faulty.
4. The
communications
port of the main
control board is
faulty.
1. Maintain or replace
the differential
pressure sensor.
2. Set the DIP switch of
the differential
pressure sensor
correctly.
3. Maintain or replace
the differential
pressure sensor.
4. Maintain or replace
the main control
board.
6.5 Parts Replacement
6.5.1 Replacing the Air Filter
Prerequisites
●
The air filter needs to be replaced.
●
Spare air filters of the same model are available and functional.
Context
The return air filter is maintained from the maintenance door.
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
6 System Operation and Maintenance
Issue 06 (2020-08-19)
Copyright © Huawei Technologies Co., Ltd.
205