Installation / Operating Instructions for 

MIDDLEMAN 

Infrared Radiant Tube Heater 

  

 

         5003356 

ETL LISTED 

COMFORMS TO 

ANSI STD Z83.20 

 

CERTIFIED TO 

CSA STD 2.34  
CSA STD 2.20 

CGA/CSA STD 2.17

 

    

  

 

                                                  

                                                  Model Numbers 

EZM-90-40 

EZUM-90-20 

EZM-90-50 

EZUM-90-25 

EZM-100-50 

EZUM-100-25 

EZM-100-60 

EZUM-100-30 

EZM-120-60 

EZUM-120-30 

 

The letter “B” added to the prefix EZM & EZUM indicates brooder model.

 

Adding the suffix LTH indicates dual input with the low input being 70% of the 
high input. 

 
The installation must comply with local codes and CAN / CGA B – 149 in Canada  
or the National Fuel Gas codes  

 
 

WARNING: 

Improper installation, 

adjustment, alteration, service or 
maintenance can cause property damage, 
injury or death. Read the installation, 
operating and maintenance instructions 
thoroughly before installing or servicing 
this equipment. 

AVERTISSEMENT. 

Une installation, un 

réglage, une modification, une réparation ou un 
entretien incorrect peut entraîner des dommages 
matériels, des blessures ou la mort. Li sez 
attentivement les instructions d’installation, de 
fonctionnement et d’entretien avant de procéder 
à l’installation ou àl’entretien de cet 
équipement. 

 

 

Содержание Middleman EZM-100-50

Страница 1: ...indicates dual input with the low input being 70 of the high input The installation must comply with local codes and CAN CGA B 149 in Canada or the National Fuel Gas codes WARNING Improper installatio...

Страница 2: ...If your gas supplier is not available call the fire department 5 Si votre fournisseur de gaz n est pas disponible appeler les pompiers 6 Do not attempt to light this or any other appliance 6 Ne pas te...

Страница 3: ...ures It is the installer s responsibility to assure that adjacent material are not subject to degradation A warning statement that an overhead heater should be installed so that the minimum clearances...

Страница 4: ...x 50 000 4 13 15 31 EZUM 100 30 oal 32 3 60 ft 100 000 2 x 50 000 EZUM 120 30 oal 32 3 60 ft 120 000 2 x 60 000 Model No Overall Length Radiant Tube Length Input Clearances to Combustibles cm Top Sid...

Страница 5: ...E TO COMPLY WITH THESE WARNINGS AND INSTRUCTIONS AND THOSE ON THE HEATER COULD RESULT IN PERSONAL INJURY DEATH FIRE ASPHYXIATION AND OR PROPERTY DAMAGE DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE...

Страница 6: ...res In case of discrepancy the latest codes standards and installation manual will take priority over prior releases WARNING Where there is the possibility of exposure to combustible airborne material...

Страница 7: ...ear any smoke from the space Notify site and safety personnel to ensure that alarm systems are not unduly activated WARNING CLEARANCES TO COMBUSTIBLES The stated clearance to combustibles represents a...

Страница 8: ...RIZONTAL HORIZONTALE 30 DEG ANGLE Above Sommet Below Dessous Side Cote Back Dos LABOUR REQUIREMENTS Two persons are required to safely install this equipment Wear gloves and other required safety prot...

Страница 9: ...s information in these installation instructions GENERAL INSTALLATION PROCEDURE PRE INSTALLATION SURVEY It is recommended that a full heating design including a heat loss calculation be conducted Heat...

Страница 10: ...The burner must be installed with the fan on the top Burner employs a ring to connect a hanging chain to stabilize the unit 5 Heaters incorporating baffles must have the baffle installed at the immedi...

Страница 11: ...1 Subsequent secondary tubes can now be joined together in the same fashion The self tapping screw holes must be adequately sealed during installation using a high temperature sealant HANGER LOCATIONS...

Страница 12: ...firing rate the greater the expansion Survey the available structural supports considering the system configuration and heat requirements of the area to establish the optimum heater location Locating...

Страница 13: ...h flexible gas connector 3 A drip leg must be installed in the gas line at the heater inlet connection tee followed by a pipe drop to the heater Failure to provide a drip leg could result in condensat...

Страница 14: ...Type 1 Hose Gas Connector CAN CGA 8 1 The heater must be isolated from the gas supply piping system by closing its individual manual shut off valve field supplied during any pressure testing of the ga...

Страница 15: ...ed for that portion of the vent that passed through the wall or roof For wall venting the manufacturer s approved vent spout or exhaust cap must be used See page 20 All models vented through a side wa...

Страница 16: ...up It is a normal condition that during heat up and cool down a tube heater will expand and contract Allowances for heater expansion must be made in the gas connection venting and combustion air ducti...

Страница 17: ...17 VENTING OPTIONS...

Страница 18: ...AC1080 Outside Air Adapter AC1030 Remote Thermostat AC1100 Outside Air Wall Cap AC1110 Combustion Air Flex Duct AC1120 4x4x6 Tee AC1130 90 degree Elbow AC1140 180 degree Bend AC1150 Wall Thimble AC11...

Страница 19: ...19...

Страница 20: ...20...

Страница 21: ...is removed from the igniter The flame sensor is utilized As long as a flame is present the valve is held open If the flame is lost the control acts to close the valve within one second and a new trial...

Страница 22: ...alve should be replaced Continued lockout of the control may indicate that the sensor is not providing the signal back to the control flame sensing circuit If the sensor is in the proper position and...

Страница 23: ...products for certain purposes which may vary among jurisdictions While Easy Radiant Works attempts to assure that its products comply with these many codes it cannot guarantee compliance or cannot be...

Страница 24: ...ompleted reports can be faxed to Technical Support Easy Radiant Works at fax no 905 899 2262 or call phone no 905 899 3473 During startup material coatings used in the production of tubes and reflecto...

Страница 25: ...25 Middleman single stage wiring diagram...

Страница 26: ...26 Middleman LTH dual input wiring diagram...

Страница 27: ...INLET GAS SUPPLY PRESSURE WITH HEATER OPERATING WC GAS VALVE OUTLET Manifold PRESSURE WITH HEATER OPERATING WC WHAT IS THE LINE VOLTAGE READING AT THE HEATER VOLTS WHAT IS THE VOLTAGE READING AT THE I...

Страница 28: ...28...