Ensure the director reporting the problem is connected to facility AC power and
the power switch (circuit breaker) at the rear of the director is set to the ON (up)
position. Inspect the director for indications of being powered on, such as:
■
At the front bezel, an illuminated power LED (green) or system error LED
(amber).
■
An illuminated green LED on the active CTP card, and illuminated green
PWR OK LEDs on both power supplies.
■
Audio emanations and airflow from cooling fans.
Is the director powered on?
YES
NO
↓
A power distribution problem is indicated. Go to “
” on page 69. Exit MAP.
6
At the director, inspect the amber LED at the top of each CTP card.
Is the amber LED illuminated on both CTP cards?
NO
YES
↓
Failure of both CTP cards is indicated. Go to “
” on page 107. Exit MAP.
7
The director-to-HAFM appliance Ethernet link failed. Perform the following:
1. At the physical map, right-click the icon with the grey square and exclamation
mark representing the director or switch reporting the problem. A pop-up
menu displays.
2. Choose the Element Manager option from the menu. The Hardware View
displays and the following occurs:
■
A grey square displays at the alert panel.
■
No FRUs are visible for the director.
■
The Director 2/140 Status table is yellow, the Status field displays
No
Link
, and the Reason field displays an error message.
Содержание StorageWorks 2/140 - Director Switch
Страница 18: ...About this Guide 18 Director 2 140 Service Manual ...
Страница 160: ...Diagnostics 160 Director 2 140 Service Manual ...
Страница 224: ...FRU Removal and Replacement 224 Director 2 140 Service Manual Figure 72 ESD grounding points 1 ...
Страница 262: ...FRU Removal and Replacement 262 Director 2 140 Service Manual ...
Страница 270: ...Illustrated Parts Breakdown 270 Director 2 140 Service Manual ...
Страница 318: ...Information and Error Messages 318 Error Messages ...
Страница 388: ...Event Code Tables 388 Director 2 140 Service Manual ...