Appendix B - Message Action List
This appendix lists all the messages that are likely to be displayed at the
control panel
. There are some fault events that are not self
clearing and will require manual intervention.
Clearable fault events
The following faults are identified as clearable fault events.
¨
FLASH corrupt
¨
Invalid device configuration
¨
Too many errors
Can be cleared but will not reset the counters.
¨
Unrecoverable Tx fault
¨
Checksum error
FLASH Configuration data and FLASH in sensors
¨
NVM recovery failures or map mis-match
How to clear a clearable fault event
To
clear
the
fault
at the control panel press the
Menu on/Off
button ->
[Test/Eng]
->
[UserCode]
-> enter your PIN (where
necessary) ->
<etc>
->
[Config
] ->
[Clear]
->
[Fault]
->
[Enter]
.
Latching fault events
The following faults are identified as latching events.
¨
Slave devices lost
¨
Loop allocation fault
¨
Invalid loop configuration
How to clear a latching fault event
To
clear
a
latching fault
it is necessary to
re-allocate
the
loop circuit
. To re-allocate a loop circuit refer to section headed
How to
power a loop
Repairable fault events
¨
Loop (partial) short circuit.
¨
Ground break
How to clear a repairable fault event
To
repair
the
fault
at the control panel press the
Menu on/Off
button ->
[Test/Eng]
->
[UserCode]
-> enter your PIN (where
necessary) ->
[Loop
] ->
<etc>
->
<etc>
->
[Repair]
->
[Loop]
-> enter the loop number on which the fault resides ->
[Enter]
.
Message Action list
The messages displayed at the
control panel or loop repeat panels
are given here in an
alphanumerical
order to provide guidance:
¨
on fault message
¨
likely meaning of the message
¨
along with suggestions on what initial actions may be taken to rectify the problem.
"
Only the messages that are applicable will appear on the display of the control panel or loop repeat panels.
¨
The term device was previously referred to as outstation.
4188-856_i2_12/06_Generic Vigilon (C VA) Comms.
97
Vigilon (EN & BS) Compact (VA) panels
Appendix
B
-
M
essage
A
ction
L