Interface input states
4 - channel interface input states
These include the mains or loop powered interface.
State
Definition
Applications
State 0
Default - all Inputs enabled
Normal use
State 1
Input 1 disabled
Selective disablement and enablement of
interface input circuits
Where an input circuit is used for
fire detection application, the call
points on the circuits will remain
operational on disablement of the
circuit.
State 2
Input 2 disabled
State 3
Inputs 1 and 2 disabled
State 4
Input 3 disabled
State 5
Inputs 1 and 3 disabled
State 6
Inputs 2 and 3 disabled
State 7
Inputs 1, 2 and 3 disabled
State 8
Input 4 disabled
State 9
Inputs 1 and 4 disabled
State 10
Inputs 2 and 4 disabled
State 11
Input 1, 2 and 4 disabled
State 12
Inputs 3 and 4 disabled
State 13
Inputs 1, 3 and 4 disabled
State 14
Inputs 2, 3 and 4 disabled
State 15
All inputs disabled
interface input disablement
Single channel interface
This include loop powered
single channel interface
and
loop powered zone module
.
State
Definition
Applications
State 0
Default - all Inputs enabled
Normal use
State 1
Input 1 disabled
Selective disablement and
enablement of interface input
circuits
Where an input circuit is used for
fire detection application, the call
points on the circuits will NOT
remain operational on disablement
of the circuit.
State 15
All inputs disabled
Interface input disablement
Generic Commissioning instructions
62
4188-856_i2_12/06_Generic Vigilon (C VA) Comms.
Device
States