Mul ti ple in puts
NOTE:
When the single channel interface unit is configured for multiple
inputs then an end-of-line capacitor unit must be used.
NOTE:
The multiple inputs may be from manual call points with
an in line 470 ohms resistor connected.
Out put cir cuit
The single channel interface unit output operation is via a relay. The relay
contacts are voltage free and rated:
q
5A at 24Vdc
NOTE:
The relay output of the interface will operate with a sector.
Therefore the single channel interface outstation will need to be configured
to a sector.
NOTE:
A local switching facility to select the input/output mode of
operation is not provided. The single channel interface unit operates both
input
and
output
circuits.
In ter face and panel out sta tions
VIG-INT-1CH Single channel interface
Vigilon Sys tem Com mis sioning