Message
associated with..
meaning..
..possible action
SAFE Address not
Set up number x
on loop y
Loop Processor Card
The replaced device is not
SAFE addressed. The
device previously installed
in the location was SAFE
addressed.
Set up the SAFE address.
Scan error
number x at
card y
Loop Processor
Card
Invalid universal scan
reply.
Check loop length and
screening
Sector actioned
Loop Processor
Card
Sector is switched
ON/OFF.
-
Sector Enabled/
Disabled at card
x
Loop Processor
Card
The sector(s) has been
enabled or disabled
automatically or manually.
If necessary , manually
enable/disable the sector
using the [Control] menu.
Sensor out of
specification
number x on Loop
y Channel z
Loop Processor
Card
Fault pattern has been
matched.
Check and replace the sensor
if necessary.
Shared memory
hardware is
faulty at Card x
Any Card
There is MCC / MCB
problem.
Replace all other cards than
the MCC/MCB. See if the
problems persists.
Replace MCC / MCB if
necessary.
Slave Device
Replaced
number x on loop
y
Loop Processor
Card
Slave type device has been
replaced.
-
Slave micro
failed at Card x
Loop Processor
Card
Loop driver is
watchdogged by loop
processor.
Reset and ignore single
occurrence. Record in log
book.
Software errors
Software errors will
activate a system
reset
Software error
Software errors will activate
a system reset.
Ignore single occurrence.
Record the event in log
book.
Sounder circuit
failed
Device
There is a fault with the
sounder hardware on the
S-cubed or S-Quad.
Replace the device
Sounder circuit
Restored
Device
The fault on the sounder
circuit associated with
S-Quad or S-Cubed has
been restored.
-
Speech circuit
has failed
Device
There is a hardware fault
possibly associated with
the voice chip on the
speech S-cubed or S-Quad
Replace the device
Speech circuit
Restored
Device
The fault on the speech
S-Quad and S-Cubed has
been restored.
-
Generic Commissioning instructions
110
4188-856_i2_12/06_Generic Vigilon (C VA) Comms.
Appendix
B
-
M
essage
A
ction
L
ist