Rotary switch
q
Set the rotary switch SW1 (on the interface board) for the required
input.
Rotary
Switch
(SW1)
position
Input circuit
function.
To monitor:
mode of input
circuit
operation
normal
status of
the input
signal
delay
(seconds)
before
signal is
accepted
0
Off
1
Off
2
Multiple inputs
Fire
N/O
0s
3
Multiple inputs
Fire
N/O
30s
4
Single input
Fire
N/O
0s
5
Single input
Fire
N/O
30s
6
Single input
Fire
N/C
0s
7
Single input
Fire
N/C
30s
8
Single input
Fault
N/O
0s
9
Single input
Fault
N/O
30s
A
Single input
Fault
N/C
0s
B
Single input
Fault
N/C
30s
C
Single input
Supervisory
N/O
0s
D
Single input
Supervisory
N/O
30s
E
Single input
Supervisory
N/C
0s
F
Single input
Supervisory
N/C
30s
N/O = Normally open N/C = Normally closed
NOTE:
An input circuit is monitored for both open or short circuit fault.
Configurations
The single channel interface unit can be configured to operate:
q
Single input
q
or Multiple input
q
with Output signal via relay change over contacts
Input/Output
line test
At an appropriate stage of commissioning the interface input and output
circuits must be tested as per project specification. The tests are based on
the type of equipment interfaced.
Sin gle in put
NOTE:
When the single channel interface unit is configured to accept
single input then a
line module
must be used.
Line module
switch
q
The line module may be installed in a remote location up to 100m cable
distance away. Its two position switch must be set to input.
VIG-INT-1CH Single channel interface
In ter face and panel out sta tions
Vigilon Sys tem Com mis sioning