Installing the cards
Setting the Rotary switch SW2
Before installing the
Loop and Network cards
onto the
MCB
ensure the rotary switch
j
SW2
is set to a required setting, see
table on the next page.
NVM hardware link P13
The NVM can be enabled or disabled by setting a hardware link
k
on the MCB. If the NVM protect is hardware disabled then it
is also possible to software enable or disable the NVM using a
[Protect] menu option under the [Setup] menu at the panel.
Unprotect:
Normally during commissioning the NVM is disabled
(unprotected) and writing to NVM is allowed.
Protect
: Once the configuration is backed up to the NVM, the
hardware link must be enable to disallow writing to the NVM.
Installing the Cards
The MCB can accommodate two Loop Cards. One Loop card
l
can be fitted into slot labelled CARD1 and the other Loop card
n
into slot labelled CARD2.
"
For a networkable system a Network Card
m
can ONLY be fitted into the slot CARD 2. Additionally the
Network Card can accommodate the second Loop card.
Earth Link
An earth link
o
is supplied with the Network Card. The link
must be fitted to the spade connector on the top edge of
MCB
with the other end to the spade connector on the
Network Card.
Battery
The lithium battery
s
is disconnected on leaving the factory by
means of an insulation disk over the top connector. The
insulation disk must be removed before powering up the system.
Terminals
Terminal blocks
p
on the top edge of the MCB are used for
wiring external circuits. The terminal block
q
on the top edge of
the PSU is used for wiring the mains supply to the panel. The
connector
r
located on the bottom edge of the PSU board is
used to connect the battery supply.
4188-856_i2_12/06_Generic Vigilon (C VA) Comms.
25
Vigilon (EN & BS) Compact (VA) panels
Vigilon
C
ompact
Panel
WARNING
REMOVAL OF COVER
EXPOSES HIGH VOLTAGE
KEYBOARD INDICATORS AND DISPLAY
L2-
0V
L2+
L1-
0V
PB1A
PB1B
P2
PP2
Network Card
Loop Card 2
P13
P13
SW1
RESET
SW2
MODE
NVM Protect - [Disabled]
NVM Protect - [Enabled]
BATT3
PB15
PB6
PB9
P2
CARD 1
IC3
KEYBOARD
IC16
POWER
SUPPLY
P12
MA2 - FS2 250mA
MA1 - FS1 250mA
P1
CARD 2
P16
P13
SW1
RESET
24V
B
A
0V
TX1 RX1 0V
PB8
MA1+ MA1- MA2+ MA2-
0V MIPNC C NO
FIRMWARE BACKUP
PB10
PB7
L1 0V L2 0V
24V
FS3 200mA
TX2 RX2
PB14
L1 0V L2 0V
NC C NO NC C NO NC C NO
PB11
new Master Control
Board (MCB)
Power Supply Unit
(PSU)
P2
P1
N
E
L
FS3 3.15A(T)
Mains fuse
P3
DANGER
FS6
1A TE5
43V
FS4
- 1A TE5
24V
P7
BAT1
FS1
- 3.15A TE5
Bat 1
Remove
insulation disk
L
N
Warning
Removal of
cover exposes
live parts
DANGER
SW2
MODE
Loop Card 1
L1+