The following procedures assume the Control panel is installed,
with cables terminated at the backbox.
¨
Open the Outer door to the enclosure using the front
door key and then open the inner door using the Allen
key located on the inside of the Outer door.
¨
Remove the protective cover fitted over the printed
circuit boards located inside the backbox.
¨
Earth Lead
Ensure the earth lead located in the top right of the
backbox is connected to the spade connector on the
inner door.
¨
DKC ribbon cable
Connect the 40-way ribbon cable from the DKC to the
socket marked KEYBOARD on the left edge of the
Master Control Board (MCB). Secure the ribbon cable
to the side of the enclosure using the cable clamp
provided.
¨
ACC DKC ribbon cable
Route the 14-way ribbon cable from the backbox on to
the inner door and connect it to the left unoccupied
socket on the ACC DKC. Secure the ribbon cable to
the inner door using the cable clamp provided.
¨
Emergency microphone cable
Connect the Emergency microphone cable to the
socket P11 labelled microphone on the bottom edge of
the ACC board. Secure the microphone lead to the P
clip on the backbox.
Generic Commissioning instructions
32
4188-856_i2_12/06_Generic Vigilon (C VA) Comms.
Vigilon
C
ompact
Voice
A
larm
Panel
Connect microphone cable
to the socket P11 labelled
microphone on ACC board
and secure cable to the P clip.
Connect 14-way
ribbon to socket
ACC DKC.
Secure 14-way ribbon to Inner door
using cable clamps supplied.
Connect the 40-way ribbon to the socket labelled
KEYBOARD on MCB and secure cable to side of
the enclosure.
Fit the earth lead to the inner door
ACC
MCB
ACC DKC
PSU
Mains terminal block
with fuse
P Clip for
mains cable
REMOVAL OF COVER
EXPOSES HIGH VOLTAGE
WARNING