Command Builds
"
Where possible use sectored action instead of
command build action.
¨
There can be up to 255 command builds per panel.
¨
a command build can only be set up with one trigger
(can be a range)
¨
a command build can be triggered:
•
for reversible action (automatic deaction on
removal of trigger)
•
or non-reversible action, (deactioned by another
command build for a non-fire trigger or reset for a
fire Trigger).
¨
the command build trigger for zone tasks reside under
the zone menu.
¨
command builds that are triggered through a sector fire
event will deaction on fire reset. This is independent of
whether the sector is configured to deaction on silence
alarms.
¨
command builds that are configured for turn Off
actions have no reverse action to turn On again,
another command build or manual action is required.
¨
command builds can be used under fire and non fire
conditions to carry out pre-configured actions built up
from the Control menu.
¨
a command build can only be set up to perform one
action (can be a range), any split range would require a
second command build.
¨
each command build can be given a 40 character label
to be displayed and/or printed when triggered. If no
label is given then nothing will be displayed
¨
if a label is given, the local buzzer will operate for 1
minute when the command build is active.
¨
command builds are logged with an On/Off time, this
information can be viewed by selecting
[info] ->
[Event]-> [Supervis]-> [Log]
and if still On via
[Info]
->
[Event]-> [Supervis]-> [Active],
this is only
possible if a label has been given to the Command
Build
¨
when speed of operation is required the lowest number
command builds should be used as these are processed
first
¨
if a digital output line is to be actioned by a command
build, the I/O line should not be assigned to a sector as
it may deaction when the silence alarms is pressed
regardless of the command build still being active
¨
a fire condition takes priority over a command build
&
Take great care not to action a digital
output to an input line, as this will effectively disable
the input.
4188-856_i2_12/06_Generic Vigilon (C VA) Comms.
123
Vigilon (EN & BS) Compact (VA) panels
Appendix
C
-
G
uidelines
for
s
tandalone
system
TRIGGER
TRIGGER
TRIGGER
TRIGGER
COMMAND
BUILD
ACTION
ACTION
ACTION
ACTION
ACTION
ACTION
ACTION
ACTION
ACTION
ACTION
ACTION
ACTION
ACTION
ACTION
ACTION
ACTION
ACTION
START MASTER ALARM
STOP MASTER ALARMS
NO ACTION
ENABLE
DISABLE
SECTOR
MASTER SECTOR
AUX RELAY
PRINTER
DIGITAL
TIME SLOT OVERRIDE
DELAY BLOCK
PAUSE SOUNDERS
RESET
LOCAL BUILD
1 TO 255
DIFFERENT
NOTE: Normally the
build reverse actions
is selected.
MENU
1ST
2ND
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
REV OR NOT-REV
REVERSIBLE
NOT-REVERSIBLE
PASSWORD
LEVELS
(CLEAR)
COMMAND BUILD FUNCTIONS
REV OR NOT-REV
COMMAND
BUILD
TIME
BLOCK
INPUT LINE
I / O INTERFACE
SECTOR
That has just
come into fire
NONE
(CLEAR)
ZONE
ONL
Y
ONE
A
CTION
FROM
EACH
C
OMMAND
B
UILD
'LABEL' OR NUMBER
UP TO 40 CHARACTERS
TASK
ONL
Y
ONE
OF
THESE
TRIGGERS
FOR
EACH
COMMAND
BUILD
SILENCE
REV OR NOT-REV
SOUND
REV OR NOT-REV
DELAY 0 TO 24 HOURS
ACTION (INPUT)
DELAY 0 TO 30 SEC
FROM ANOTHER ZONE
TRIGGER
CHANNEL
Integral
sounder
TRIGGER
SOUNDER
INTEGRAL
SOUNDER IN OHS
ACTION
REV OR NOT-REV
VERIFY
ACTION
REV OR NOT-REV
TONE/ MESSAGE
AUX MESSAGE
ALARM MESSAGE
Sound
Silence
Reset
ASSIGN
ASSIGN
ASSIGN
Sound
MASTER
SECTOR
TRIGGER