Message
associated with..
meaning..
..possible action
Master alarm
enabled/disabled
MCC / MCB (main
control card/board)
The master alarm has been
enabled or disabled
automatically or manually.
If necessary, manually enable
or disable the master alarm
using the [Control] menu.
Master alarm
restored
Power supply
Master alarm fault cleared.
The ADC value should be
74.
Master
polling/not
polling at
card x
MCC / MCB
PC or SRI (service request
interface) is not
handshaking with the
control panel
Check the wiring
Master Sector
Actioned
MCC / MCB (main
control card/board)
Master sector has been
switched ON/OFF.
-
Master Sector
Enabled/Disabled
MCC / MCB (main
control card/board)
Master sector has been
enabled or disabled
manually or automatically.
If necessary manually enable
or disable the master sector.
Memory corrupt
number x loop y
Device
FLASH checksum failure
Replace the device
Message
discarded
TBA
TBA
TBA
Neighbour ACK
Failed at card n
-
Repeated address
Check domain addresses are
unique
Neighbour ACK
Invalid at
card n
TBA
TBA
TBA
Network
initialised at
Card x
Network Card
Successful network map
with polled panels.
-
Network Insecure
/ Secure at
Card x
Network Card
There are 3 missing replies
in a row on End-2 of the
controller.
Check the wiring.
Check the error rate.
Network starting
at Card x
Network Card
Communication starting
with other connected
panels.
-
Network wiring
fault at card x
Network Card
Wiring is presumed to be
oc between
panel n and panel n.
Check the wiring.
New address n at
card x
MCC / MCB
Network Card
The new address set has
been read.
-
New domain
address n at
Card x
Network Card
The new address set been
read at the particular card.
-
NMI’s missed at
card x
Loop Processor
Card
Software error.
Software errors will activate
a system reset.
Ignore single occurrence.
Record the event in log
book.
4188-856_i2_12/06_Generic Vigilon (C VA) Comms.
107
Vigilon (EN & BS) Compact (VA) panels
Appendix
B
-
M
essage
A
ction
L
ist