Message
associated with..
meaning..
..possible action
Call point glass
is broken
number x loop y
Device
Call point has been
operated when the device is
disabled.
Replace the glass, if
necessary.
Call point on
interface unit
operated/
restored
Device
Mains powered interface
input has been triggered by
conventional MCP. Value
of input is equal to or less
than 6V.
-
Call point open
cct number x on
loop y
Device
Monitored base does not
see end-of-line unit. There
is a bad connection to
MCP.
Check the internal wiring,
there may be a loose
connection.
Call point
operated/restore
d number x
loop y
Device
Break glass has been
broken or operated with a
test key.
Replace the break glass to
restore the call point or
remove the test key,
whichever is applicable.
Call point short
cct number x
loop y
Device
Call point contacts are
short circuit.
Check the call point contacts
and circuit internally.
Card found/lost
at card x
Any Card
The card has been
found/lost. If lost then it is
locked out.
There may be a hardware
fault on card or Bckplane.
Investigate and rectify.
Card n recovered
/Card n backed
up
Memory (NVM) -
Backplane
Data recovered to a card
from the NVM. A card data
has been backed up to the
NVM.
-
Chamber Removed
/Replaced number
x on loop y
Device
Device chamber has been
removed.
Replacing the chamber will
cause a replaced indication.
Charger Fault
Panel
Power Supply Unit
(PSU)
Charger circuit has failed.
Replace the PSU.
Charger Fault
number x on
loop y
EN54 System device
power supply
(Repeat, Mimic or
mains powered
interface)
Charger circuit has failed.
Replace the board (having the
power supply) on the loop
device.
Charger Restored
Panel power supply
Charger circuit is working
again.
-
Charger Restored
number x on
loop y
EN54 System device
power supply
(Repeat, Mimic or
mains powered
interface).
Charger circuit is working
again.
-
Chk=4.874 NVMC
41874 Flag=0
NVM is write
protected at
Card x
Memory (NVM) -
Backplane
The memory is read only.
Disable the write protect
using the [set up] menu.
Generic Commissioning instructions
100
4188-856_i2_12/06_Generic Vigilon (C VA) Comms.
Appendix
B
-
M
essage
A
ction
L
ist