
Indications on power up
These are typical power up indications given at the panel with no
loop circuits connected. For Vigilon Compact VA panel the audio
loop must remain disconnected at this stage.
¨
Switching on the mains power to the panel and
connecting the battery supply:
•
the panel buzzer sounds
•
some LEDs on the panel will be momentarily lit
•
a message is displayed.
Powering up - please wait
........
•
the dots below the powering up message is a
progress indicator.
•
the
Disablement
light gives a flashing indication
and after a short duration changes to a steady
indication.
•
the display gives messages similar to:
Time not set
NVM Card Fitted
Audio Card Keypad fitted
-(Compact VA)
NVM is not write protected
Card found at Card 1 x.xx (aa/bb/cc)
Allocating Loop n
ACC Loop O/S 2
•
NVM Card is the Non Volatile Memory (NVM)
Card
•
Card 1 is always a Loop card
•
Card 2 message will only appear if an optional
loop card is fitted in CARD 2 slot of the Master
control board (Vigilon compact or compact VA
only)
•
the x.xx is the software version number of the card
•
the aa/bb/cc signifies the day month and year of
software release.
Allocation: OK at Card X : Nothing
found
There may be other indications and messages depending on the
panel condition.
•
Disablement
indicator is lit.
Initial tests
"
The menus at the control panel are accessible
by pressing the Menu On/Off button. For details of all the
menu options see Appendix A - Menu Maps .
Display test
¨
To test the display press the
Menu On/Off
button and
then select
[Test/Eng]
->
[Disp Test].
The
Display Test
option will cause all the LEDs and buzzer (including
backlight) to remain On for a short duration.
Setting the Clock
¨
To set up the time and date, press the
Menu On/Off
button and then select
[SetUp]
->
[Set Clock].
The
Set
Clock
option will allow the setting of the time and date
at the panel.
Printer test (if fitted)
¨
To test the printer press the
Menu On/Off
button and
then select
[Control]
->
[Printer],
if the printer is On
select
[Test]
to carry out a printer test.
Power supply test
¨
Test the panel’s mains and battery supply by carrying
out temporary disconnection and reconnection, to
allow an indication of the events to be given on the
panel. Ensure sufficient time is given for the event to
be displayed, normally within 2 minutes.
Master alarms circuit tests
¨
Check that indications are given when there is a fault
on the master alarm circuit. Carry out an open circuit
test by disconnecting the end of line resistor. Then
carry out a short circuit test by shorting the master
alarm circuit terminals.
Generic Commissioning instructions
38
4188-856_i2_12/06_Generic Vigilon (C VA) Comms.
Indications
on
power
up