Panel Buzzer
¨
It may be necessary during commissioning to switch
Off
the panel buzzer. It is possible to selectively switch
the disablement, fault, fire, supervisory and command
build buzzer sound to
Off
or
On
. It is important to
ensure that the buzzer is switched
On
for normal
operation after commissioning.
Fire plan
¨
The system should be tested in accordance with the
project specification.
Sensor cover
¨
Each fire sensor installed in the system should have
been fitted with a
dust cover
during installation. The
dust covers must be removed from all the fire sensors
after the panel loops have been satisfactorily
powered-up and with addresses allocated to each
device ready for further checks and tests.
Site specific installation
¨
Plant equipment interfaced to the system should be
tested to recommendations made in the project
specification.
Test mode (V4) & Commission Mode (V3+)
¨
During commissioning of the system you will need to
switch
On
the Test/Commission mode. It is important
to switch
Off
the test/commission mode after the work
is over, to ensure the system operates normally.
Informing responsible persons
It is important to inform the
person(s) responsible
for the fire
alarm system that the system is being commissioned.
Pre-commissioning
¨
Check the installation of fire alarm equipment with
reference to the most recent
as fitted wiring drawings.
¨
Get the feel of the operating condition of areas on the
site:
•
action the installer to carry out any rectification
work plus
•
report discrepancies for administration purposes.
¨
Where the operating condition of an area is not right
for the equipment installed, then the appropriate
replacement action must be taken.
¨
Ensure the fire system equipment is installed in
accordance with the appropriate standards and project
specification.