Factory settings
The factory settings of the panel are described here.
P0 - RS485, Baud: 1200 Mode: Repeat
(dedicated for repeat indicator panel)
P1 - RS232, Baud: 9600, Mode: Standard
P2 - RS485, Baud: 9600, Mode: Standard
NVM - software write allowed (NVM protect -disabled)
hardware write allowed (NVM protect -disabled)
NVM hardware link P13
System configuration
Domain address - 0
Panel (Node) address - 1
All devices assigned to sector 1
All devices assigned to zone 1
Sector 1 is assigned to all ten voice alarm zones
Loop Processor Card (LPC)
A Loop Processor Card (
part number : COMPACT-LPC
) is able
to control up to 200 devices connected onto a loop circuit. The
LPC drives the loop circuit from both ends, and handles all
messages to and from each device. The control panel can
accommodate up to 2 LPCs.
¨
Fit the Loop Processor Card in Card 1/2 slot on the
MCB.
4188-856_i2_12/06_Generic Vigilon (C VA) Comms.
35
Vigilon (EN & BS) Compact (VA) panels
Vigilon
C
ompact
Voice
A
larm
Panel
P15
P10
P11
P9 P8
P2
CARD 1
IC3
KEYBOARD
PRINTER
IC16
POWER
SUPPLY
P12
MA1 - FS1 250mA
MA2 - FS2 250mA
P1
CARD 2
P16
P13
SW1
CODE
BCKUP
Loop Card
Master Control Board
P7
P6
24V
FS3 200mA
P14
'
Factory setting is NVM protect
disabled
Hardware' NVM protect link P13
NVM protect - [Enabled]
(ie NVM protected,
that is
)
write not allowed
NVM protect - [disabled]
(ie NVM unprotected,
that is
)
write allowed
BATT1
Connector P1 Plugs into the MCB
Local Processor Card
IC4 Loop
Processor