IO card location
One new IO card is normally fitted as Card 15 in socket P2 of
the Control panel backplane.
Setting switches SW1 and SW2
"
IMPORTANT:
The Vigilon Control Panel make use of the DIP switches
on the DKC, located on the inner door. The switches are
used to set address and baud rate. It is important that the
DIP switches SW1 on the IO card are ALL set in the UP or
OFF position so that they are ignored.
SW1 Switch settings
The switch positions shown here are applicable for the new IO
Card when installed as an additional IO card.
"
No dongle is required for DIP switches to
work when used as second or additional IO card.
Baud Rate
Node Address
1
2
3
|
4
5|
6
7
8
|
Off Off Off 1200 baud
Off Off Off Off Off
Off Off On
1800 baud
Off Off Off Off On
1
Off On Off
2400 baud
Off Off Off On Off
2
Off On On
3600 baud
Off Off Off On On
3
On Off Off
4800 baud
Off Off On Off Off
4
On Off On
7200 baud
Off Off On Off On
5
On On Off
9600 baud
Off Off On On Off
6
On On On
19200 baud
Off Off On On On
7
|
On On On On On
up
to
31
Factory settings
SW2 Switch settings
Rotary
Switch
Pos.
Standard connections
Port 0 (RS232) Mode
Port 1
(RS485 mode
0
3217 Half/Full-Duplex
Switch
position from
0 to 7 sets this
port for
Repeat panel
at 1200 baud.
Switch
position from
8 to F sets
this port for
other
applications
at 9600 baud.
1
Slave I/O
2
Remote Printer (as
VIG-IOC-PRT)
3
Universal Full-Duplex (as
VIG-IOC-UFD)
4
Ascom Pager (as
VIG-IOC-ASCOM)
5
Domain Bridge Full-Duplex
6
Universal Half-Duplex (as
VIG-IOC-UNI)
7
-
Factory setting
Installation instructions
new IO Card EN54 (VIG-IOC-DOM)
Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without
obligation to notify any person of such revisions of changes.
Hamilton Industrial Park, Waterside Road, Leicester LE5 1TN, UK.
Website: www.gent.co.uk
Tel44 (0) 116 246 2000
Fax (UK): +44 (0)116 246 2300
2
new IO Card (EN54) 4188-777 issue 3_11/05
by Honeywell
To DKC
40 way ribbon
cable
20 way ribbon
cable
Local Controller card
Input/Output card
Loop Processor card
Space for 3 Loop
Processors
Network card
P1
P4
LCC - P1
IOC- P2
LOOP 1 - P3
LOOP 2 - P4
LOOP 3 - P5
LOOP 4 - P6
P7
P8
Backplane
P3
1 2 3
On
Off
8
7
6
5
4
3
2
1
SW1
SW2
IC4
P2
new IO Card
Factory
set to 5