Delay Blocks
¨
There can be up to 16 delay blocks per panel
¨
each delay block can provide a delay of between 4 seconds to 10 minutes (in 4 second increments) before starting a
desired action
¨
a delay block can action:
•
sectors
•
delay blocks
¨
a delay block may be actioned by:
•
sectored fire event
•
command build
•
delay blocks
¨
if the required delay is beyond 10 minutes. This can be achieved by a delay block actioning another delay block
before the required action is taken
"
If Delay Blocks are linked to produce a delay of longer than 10 minutes, then the panel will no longer meet the
requirements of EN54: part 2:1997.
¨
where a delay block is actioned by a command build, a different delay time is set up (within the command build
entry line).
4188-856_i2_12/06_Generic Vigilon (C VA) Comms.
119
Vigilon (EN & BS) Compact (VA) panels
Appendix
C
-
G
uidelines
for
s
tandalone
system
COMMAND
BUILD
DELAY BLOCK FUNCTIONS
SECTORS
SECTORS
10 MINS
MAX
DELAY
BLOCK
10 MINS
MAX
ANOTHER
ACTION
ACTION
ACTION
16 DELAY
BLOCKS
PER-PANEL
DELAY
BLOCK
ACTION
SIGNAL
1
2
SIGNAL
3
SIGNAL
ALL
SIGNALS
OFF
ACTION
SET UP
NOTE : THIS CONFIGURATION IS POSSIBLE
A delay block
actioned from a
command build can
have a separate
delay of up to
10 minutes
NO
ACTION
ON
ON
ON
OFF
OFF
OFF
NOTE: If no sectors are set up to be actioned
but there is a signal number set up and the
original trigger was from a sector, then
when the delay times out that sector will
be actioned.