# - Default state
S-Quad Dual Optical Heat / Optical Heat sensor states
State
Definition / Class
Application / Suitable for:
State 0#
Medium sensitivity optical,
Class A1 heat
General application
State 2
Low sensitivity optical,
Class A1 heat
Application with moderate dust, smoke or steam is present
State 3
High sensitivity optical,
Class A1 heat
Clean environments (where early detection is required)
State 5
Medium sensitivity optical,
Class B heat
High ambient temperature plus low dust or smoke or steam
present
State 6
Low sensitivity optical,
Class BS heat
High ambient temperature with change, plus moderate
dust, smoke or steam present
State 8
Delayed medium sensitivity
optical, Class A1 heat
General application with transient steam dust or smoke
present
State 11
Low sensitivity optical,
Class B heat
High ambient temperature where moderate dust, smoke or
steam present
State 12
Class A1 heat only
Smoke, dust or steam occurring often
State 15
No detection
S-Quad Dual Optical Heat CO sensor states
State
Definition / Class
Application / Suitable for:
State 0#
Medium sensitivity optical,
Class A1 heat, Medium sensitivity gas
(false alarm resistant)
General application where false alarm
reduction is required
State 1
High sensitivity optical, Class A1 heat,
high sensitivity gas
Clean environments (where early detection is
required) false alarm reduction
State 9
Medium sensitivity gas,
Class A1 heat
High levels of smoke/dust/steam often present
State 11
Medium sensitivity optical,
Class B heat
High ambient temperature, plus low levels of
dust/smoke/steam
State 12
Class A1 heat only
Smoke/dust/steam/gas occurring often
State 15