Appendix D - Guidelines for Networked system
commands
These functions apply to networked systems. See also guidelines for standalone system.
"
For information on Command build actions across a network, see Appendix C.
When commissioning a network of control panels, ensure the software version is same across all the panels. This is
also applicable when an existing network is to be installed with additional panels.
Master Sectors
¨
There can be up to a maximum of 64 Master Sectors per panel
¨
a total of 255 master sectors per network system
¨
they are therefore a collection of:
•
Sectors
•
Delayblocks
•
Master Alarms
•
and Aux Relays from one or more Systems.
¨
they provide global alarm actions across a network of control panels
Generic Commissioning instructions