2nd Fix Installation
Repeat panel 2nd fix part
Quantity
À
Outer door assembly
1
Á
Inner door assembly
1
Â
Master Repeat Card
1
Ã
20 Way ribbon cable
1
Ä
40 Way ribbon cable
1
Å
Spares pack (includes battery leads)
1
a
Remove the protective temporary cover from the
backbox.
b
Fit the inner door
Á
to the repeat panel
enclosure, remembering to connect the earth
lead to door and then fit the outer moulded door
À
.
c
Fit the Master Repeat Card into the backbox
and:
•
connect the transformer wires to terminal
block - P10.
•
connect battery wires
Å
supplied with the
spares to terminal block P9 (note the red wire
connects to the + and black wire to the -
terminal respectively).
•
connect the ribbon cable from the terminal
card to connector - P14 on Master Repeat
Card.
•
connect the 40 way ribbon cable
Ä
from
Master Repeat Card connector P7 to Display
Key Card connector - P1.
•
connect the 20 way ribbon cable
Ã
from
Master Repeat Card connector P8 to Display
Key Card connector - P6.
d
Power-up the panel by connecting the mains
supply and then the battery supply, and note:
•
the green and amber LEDs on the Master
repeat card are lit
•
all lights on the panel facia are lit for a short
duration
•
a reset message appears on the display
•
the local buzzer sounds for a short duration
•
a battery disconnected message appears
•
the display shows:
MAIN PANEL OFF LINE
•
the System Fault LED is lit on the panel facia
EN54 Repeat inst. 4188-839.03_11-06
3
Vigilon Repeat panel (EN)
Data and installation instructions
Danger
MASTER
REPEAT
CARD
BACK BOX
FS1
2.5A
Auxiliary
supply fuse
2.5A
Battery fuse
FS2
12V 7Ah battery
D10
Red LED
(Loop communications)
D6
Yellow LED
(Watchdog)
D9
Green LED
(Power ON)
AC
AC
P10
P9
Transformer
MAINS
TERMINAL
BLOCK
L
E
N
P14
P7
P8
P21
P20
CAUTION
HAZARDOUS VOLTAGES REMAINS
AFTER OPERATION OF FUSE.
ESD
BONDING
POINT
RED
BLACK
+VE 0V
0V V
SW1
RESET
SWITCH
TERMINAL
CARD
FILTER
MAINS
FUSE
EARTH
LEAD TO
INNER
DOOR
DKC
SELECTION
LINKS