HLP-A100 Series Operating Manual
HLP-A100 Series
-
96
-
Function: Enter VI Low Voltage corresponding to Min. reference/feedback
set in C06.14.
C06.1* Analoge Input 1
C06.10
Function Description
Range
Unit
Default Setting
Terminal VI Low Voltage 0.00~9.99
V
0.07
Function: Enter VI High Voltage corresponding to Max. reference/feedback
set in C06.15.
C06.11
Function Description
Range
Unit
Default Setting
Terminal VI High voltage 0.10~10.00 V
10.00
Function: Enter VI Low Current corresponding to Min. reference/feedback
set in C06.14.
C06.12
Function Description
Range
Unit
Default Setting
Terminal VI Low Current 0.00~19.99 mA
0.14
Function: Enter VI High Current corresponding to Max. reference/feedback
set in C06.15.
C06.13
Function Description
Range
Unit
Default Setting
Terminal VI High Current 0.01~20.00 mA
20.00
Function: Enter VI Low Ref./Feedb. Corresponding to Min. voltage or min.
current set in C06.10 or C06.12.
C06.14
Function Description
Range
Unit
Default
Setting
Terminal VI Low
Ref. /Feedb.
-4999.000~4999.000
0.000
Description of Choice: To active the Live Zero Timeout Function, if voltage
input is selected, then the low input voltage (C06.10, C06.20) settings
must be greater than 1V; if current input is selected, the low input
current (C06.12, C06.22) settings must be greater than 2mA or
more. If the analog input signal is lower than 50% of the settings of
parameters of C06.10, C06.12, C06.20, C06.2, and lasts longer than the
settings of the parameters of C06.00, this feature take effect.