HLP-A100 Series Operating Manual
HLP-A100 Series
-
100
-
Option: [0] Voltage mode;
[1] Current mode;
Function: Select the input to be present on analog input AI.
C06.29
Function Description
Range
Unit
Default Setting
Terminal AI Mode
0~1
0
Option: [0] 0-20mA;
[1] 4-20mA;
[3] 0-10V;
Function: Select output to be present on analog output VO.
Attention: This parameter is in relation with the jumper switch, if voltage
output is selected, leg1
、
2 should be asserted on; if current output is
selected, leg2
、
3 should be asserted on.
C06.7* Analog Output VO
C06.70
Function Description
Range
Unit
Default Setting
Terminal VO Mode
0~3
3
Option: [0] No operation;
[10] Output f requency, (0-10V) or (0/4-20mA) corresponding to
0-200Hz;
[11] Reference: C03.00 choose“0” [Min. – Max.] , 0% = 0 mA, 100% =
20mA. C03.00 choose [1] [-Max. – Max.] , -100% = 0 mA, 0% = 10mA,
+100% = 20 mA;
[12] Feedback, (0-10V) or (0/4-20mA) corresponding to -200% ~ 200%;
[13] Motor current, (0-10V) or (0/4-20mA) corresponding to 0-Max
motor current, see C16.37;
[16] Power, (0-10V) or (0/4-20mA) corresponding to 0-motor
f requency, see C01.20;
[17] Motor speed, (0-10V) or (0/4-20mA) corresponding to 0-motor
speed, see C1.25;
[18] Output voltage, (0-10V) or (0/4-20mA) corresponding to 0-motor
voltage, see C1.22;
[20] Bus control (0-10V) or (0/4-20mA) corresponding to 0.0% -
100.0%, 100% equals to reference in C03.03;
[21] Pulse input (0-10V) or (0/4-20mA) corresponding to reference
f rom C05.55 to C5.56 transmitted via terminal DI4;
C06.71
Function Description
Range
Unit
Default Setting
Terminal VO Analog
Output
0~23
0