HLP-A100 Series
HLP-A100 Series Operating Manual
-
83
-
C04.31 Function Description
Range
Unit
Default Setting
Motor Feedback
Speed Error
1~600
Rpm
300
Function: Select the max allowed tracking error in speed f rom calculated and
the actual mechanical motor shaf t output speed.
C04.32 Function Description
Range
Unit
Default Setting
Motor Feedback Loss
Timeout
0.00~60.00
S
0.05
Function: Set the timeout value allowing the speed error set in C04.31 Motor
Feedback Speed Error to be exceeded. If the motor feedback signal
interrupts within this timeout value, the timer resets.
C04.5* Adj. Warnings
This parameter group is used to adjust warning limits for current
、
speed
、
reference and feedback . Warnings that are shown on the display can
be programmed as an output or sent via serial bus.
C04.50 Function Description
Range
Unit
Default Setting
Warning Current Low
0.00~I
max
A
0.00
Function: Enter the I
low
value, when the motor current falls below this limit, the
display reads current low. Setting range depends on the motor size.
Attention: This setting must be within normal motor current range, otherwise,
it may produce an error warning.
C04.51 Function Description
Range
Unit
Default Setting
Warning Current High
0.00~I
max
A
Function: Enter the I
high
value, when the motor current exceeds this limit, the
display reads current high. Setting range and default setting depend
on the motor size.
Attention: This setting must be within normal motor current range, otherwise,
it may trigger an error warning.
C04.52 Function Description
Range
Unit
Default Setting
Warning Speed Low
0.0~400.0
Hz
0.0
Function: Enter the n
low
value, when the motor speed falls below this limit, the
display reads Speed Low.
Attention: This setting must be within normal motor f requency range,
otherwise, it may trigger an error warning.