HLP-A100 Series Operating Manual
HLP-A100 Series
-
82
-
C04.30 Function Description
Range
Unit
Default Setting
Motor Feedback Loss
Function
0~11
1
4
C04.21 Function Description
Range
Unit
Default Setting
Max Output Frequency
Resource
0~21
0
1
*C04.19 Function Description
Range
Unit
Default Setting
Max Output Frequency 0.0~400.0
Hz
65
Function: Enter value of the maximum output frequency.
Option: [0] No operation;
[1] Freeze output;
[3] Jog;
[4] Operating at the max.output f requency;
[5] Stop and warning;
[11] Open loop running;
Function: Select which reaction the f requency converter should take if a
feedback fault is detected.
Attention: When in HAND mode, and Speed-closed loop is selected, options [1]
、
[3]
、
[4] are invalid.
Option: [0] No f unction, no reference resource is defined;
[1] Analog in VI, use signals f rom Analog input VI as reference
resource, see C06.1*;
[2] Analog in AI, use signals f rom Analog input AI as reference
resource, see C06.2*;
[8] Pulse input, use signals f rom Pulse input (DI4) as reference
resource, see C05.5*;
[11] Local bus reference, use signals f rom Local bus reference as
reference resource, see C08.9;
[21] LCP potentiometer, use signals f rom LCP potentiometer as
reference resource, see C06.8*;
Function: Use an analog input to calibrate max output f requency
(C04.19) f rom 0 to 100%, like in analog input calibration parameter
(C06.1*). This parameter only be enable when C01.00 = 4.
C04.3* Motor Feedback Monitor