HLP-A100 Series
HLP-A100 Series Operating Manual
-
175
-
Field
Description
01
FC address
05
Function
00 40
0x0040 convert to decimal number is 64.The register address
64 is parameter write control
FF 00
0000-Parameter changes are written to the RAM;
FF00- Parameter changes are written to the RAM and
EEPROM;
8D EE
CRC check
Field
Description
01
FC address
05
Function
00 40
0x0040 convert to decimal number is 64.The register address
64 is parameter write control
FF 00
0000-Parameter changes are written to the RAM;
FF00- Parameter changes are written to the RAM and
EEPROM;
8D EE
CRC check
Example:write parameter to RAM and EEPROM
Transmit: 01 05 00 40 FF 00 8D EE(Hexadecimal)
Receive: 01 05 00 40 FF 00 8D EE(Hexadecimal)
Example: set C01.01 = 1
Transmit: 01 06 03 F1 00 01 19 BD(Hexadecimal)
Receive: 01 06 03 F1 00 01 19 BD(Hexadecimal)
Transmit data
Receive data
12.5 Force Single Coil
12.6 Preset Single Register