HLP-A100 Series
HLP-A100 Series Operating Manual
-
63
-
C01.55 Function Description
Range
Unit
Default Setting
V/F Characteristic-V
0~999.9
V
0/Vn
Function: This parameter is an array parameter [0-5], used for setting
voltage [V0-V5] at each frequency point to manually form a V/
F characteristic matching motor. Frequency points are defined in
par. C01.56, V/F characteristics - F.
Description of choice: This parameter is only functional when par.
C01.01, Motor Control Principle is set to V/F [0].
Attention: V0 factory setting is set to 0V, and U1-U5 factory setting is set
to Un (motor rated voltage) .
C01.50 Function Description
Range
Unit
Default Setting
Motor Magnetisation
at zero speed
0~300
%
100
Function: Enter a percentage value of the rated magnetizing current.
Description of the choice: Use this par. with par. 1-52 to obtain a different
thermal load on the motor when running at low speed.
Attention: If the setting is too low; the torque on the motor may be
reduced.
C01.52 Function Description
Range
Unit
Default Setting
Min Speed Normal
Magnetizing
0.0~10.0
Hz
100
Function: Set the required frequency for normal magnetising current.
Use this par. along with par. 1-50.
Attention: If the frequency is set lower than the motor slip frequency, par.
C01.50 is inactive.
C01.5* Load Indep.Setting
Содержание HLP-A100 Series
Страница 1: ......
Страница 2: ...HLP A100 Series Operating Manual...
Страница 3: ......
Страница 7: ...HLP A100 Series Operating Manual HLP A100 Series 6...