*C14.40 Function Description
Range
Unit
Default Setting
VT Level
40~90
%
90
Function: Selection of a proper value reduces energy loss in the motor.
*C14.41 Function Description
Range
Unit
Default Setting
AEO Min. Magnetisation
40~75
%
66
Function: Enter the minimum allowable magnetization for AEO, selection
of a low value reduces energy loss in the motor, but can also reduce
resistance to sudden load changes, and the output power increases.
C14.4* Energy Optimising
C14.30 Function Description
Range
Unit
Default Setting
Current Controller
Proportional Gain
0~500
%
100
C14.31 Function Description
Range
Unit
Default Setting
Current Controller
Integration Time
0~2
S
0.02
C14.32 Function Description
Range
Unit
Default Setting
Current Controller
Proportional Gain
0~100
ms
1
Function: Current Controller Proportional Gain, choose a higher value
causes the controller response more quickly, but too high will
cause the controller unstable.
Function: Current Controller Integration Time, the lower the value setting,
the more rapid reaction of the torque limit controller, but too low
setting will cause the control not stable.
When the current limit is reached during motor or generator work, the
inverter will try to reduce current below limit as soon as possible while not
losing the control of the motor.
When the controller is enabled, the inverter can only be stopped by
setting a digital input to coast or coast and reset (inverse). Unless the inverter
is no longer near the current limit, otherwise any signal on C05.10-C05.15
terminal will be invalid.
When use digital terminal which is set to coast or coast and reset (inverse)
f unction, the motor will not stop according to ramp time. so if need quick
stop, please use external electro-mechanical braking system.