HLP-A100 Series Operating Manual
HLP-A100 Series
-
176
-
Field
Description
01
FC address
06
Function
03 F1
The register address of C01.01 is 101*10-1=1009(0x03F1)
00 01
The parameter value is 1
19 BD
CRC check
Field
Description
01
FC address
06
Function
03 F1
The register address of C01.01 is 101*10-1=1009(0x03F1)
00 01
The parameter value is 1
19 BD
CRC check
Field
Description
01
FC address
0F
Function
00 00
Register address 0 is frequency converter control word.
00 20
The bit number is 32.
04
The byte number is 4
7C 04
Control word. “7C 04”swap high byte and low byte, the
value is 0x047C
Note:
0x047C convertes to binary is: 0000 0100 0111 1100 are
corresponding to the coil address 0-15
Example: the frequency is 40% of C03.03.
Transmit: 01 0F 00 00 00 20 04 7C 04 9A 19 37 B3(Hexadecimal)
Receive: 01 0F 00 00 00 20 54 13(Hexadecimal)
Transmit data
Receive data
Transmit data
12.7 Force Multiple Coils