E.11
Motor Over
Temperature
Thermistor damage,
uncorrectly installed or
motor cooling equipment
failure.
A.12
E.12*
Torque Limit
Torque exceeds the max.
torque limit.
A.13
E.13*
Over Current
Inverter peak current limit
is exceeded.
A.14
E.14*
Earth fault
Discharge from output
phases to ground(22KW
and below)
E.16*
Short Circuit
Short circuit in motor or on
motor terminals.
A.17
E.17
Control Word
Timeout
Drive communication
timeout, this alarm occurrs
when C08.04 is set to 0 or 5.
A.24
E.24
Fan Fault
Too much dust on the fan
or the fan is aging.
E.25*
Brake resistor
short-circuit
Brake resistor is short
circuit, leading the brake
f unction invalid.
E.27
Brake transisitor
short-circuit
Brake transistor is short
circuit leading brake
f unction invalid.
E.28
Brake Detect
Brake resistor is not
connected or working.
E.30*
Motor phase U
missing
Motor phase U is missing,
check the phase.
E.31*
Motor phase V
missing
Motor phase V is missing,
check the phase.
E.32*
Motor phase W
missing
Motor phase W is
missing,check the phase.
E.38*
Internal Fault
Contact the local distributor
or Holip Company.
E.44*
Earth Fault
Discharge from output
phases to ground(22KW or
more)