HLP-A100 Series Operating Manual
HLP-A100 Series
-
160
-
7.13.2 Parallel Execution
The following figure shows parallel execution mode of four events/actions:
Example:
1. Start event
C13.01 = [33] Enter the start event via digital input terminal FOR;
C13.00) = [2] Simple PLC parallel control mode;
C13.02= [20] the inverter issues an alarm and trips to stop.
2. Event/Action:
Event status 2(C13.51 [2]) = [34], entered via terminal REV;
Event status 3 (C13.51 [3]) = [40], the drive stops in any way;
Action 2(C13.52 [2]) = [22] If the REV input is true, then, start the drive;
Action 3(C13.52 [3]) = [40] If the drive has stopped, reset counter A;
Note: If event 2 is true, action 2 will be executed; if event 2 is false, but
considering terminals
、
local bus excites the inverter to stop, action 3 will be
executed.
3. Stop Event:
If stop event /C13.02 is true, Simple PLC will be disabled, and C16.38 will
be reset to 0.
Parameter Ref. Function Parameter Ref.
Function
C13.51[21]
53
Simple
PLC Time-
out 6
C13.52[21]
69
Start Timer 7
C13.51[22]
C13.52[22]
17
Select Preset ref 7
C13.51[23]
C13.52[23]
21
Select Ramp 4
C13.51[24]
54
Simple
PLC Time-
out 7
C13.52[24]
1
No Action
If C13.52 [24] is set to “stop”, the internal control eight-speed will perform
only one week, not cycles.